3 Configuring the redundant peripherals
3.9 CFC configuration
Activity
6.
If necessary, edit additional symbols
and save your entries by clicking the
"OK" button.
The dialog box "Edit Symbols" is closed.
7.
Select each signal module, one after the
other, in the module overview and assign
them symbolic names. To do this, follow the
steps 2 to 6.
3.9
CFC configuration
Once you have completed the necessary configurations, you have to create
CFC charts. In this step you connect the input/output modules you added in the
HW Config with the corresponding channel blocks.
Requirements
All the required I/O modules have been configured in the HW Config and
the associated symbols have been assigned.
The CFC chart has been created and is open.
Procedure
Table 3–11
Activity
1.
Select the "Libraries" tab In the lower left
pane. Select the path "PCS 7 AP Library
V81 > Blocks+Templates\Blocks >
Channel".
Now drag the driver module Pcs7AnIn,
Pcs7AnOu, Pcs7DiIn or Pcs7DiOu and
drop it into your plan, depending on the
input/output module.
2.
To connect further building blocks, drag
them into your plan. For example, if you
want to measure temperature, you can
connect the channel block with a MonAnS
or MonAnL, which allow the measured
temperature to be displayed later on during
operation.
3.
To connect the channel module with its
configured I/O module, select the block,
click on "PV_In" of the channel block and
open the menu command "Insert >
Connection to Address".
The symbol table opens.
Configuration of Redundant I/O Modules
Entry-ID: 28430682,
V2.0,
03/2015