Siemens SIMOVERT Masterdrives SSB Operating Instructions Manual page 29

Safe stop board
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
02.2000
♦ Mounting types ≥ J
The "SSB" board is inserted at connector X258 of the power supply. The ribbon cable to the electronics box is
now connected at connector X538 on the "SSB". The mounting position of the power supply can be seen from
Fig. 2.3.
Fig. 4-6
1.
Bolt the mounting bracket to the "SSB".
Insert the cable (Fig. 4-6)
Siemens AG 6SE7080-0AX87-1JB0
Safe Stop Board
Operating Instructions
6SE7090-0XX84-1HK0
476 479.9000.00
Fig. 4-7
2.
Power-down the SIMOVERT MASTERDRIVES!
Do not forget the 230 V AC fan power supply.
Check that the DC link is discharged!
Remove the electronics module by releasing the two
bolts a).
Caution:
Do not withdraw the electronics module too far! Do
not subject the connector cables to any stressing! The
electronics module must not be drawn out so far that
it will fall!