Setting Up the MJ-4A & MJ-4B Control Panel
4 Setting Up the MJ-4A & MJ-4B Control Panel
4.1
Setup—Overview
MJ-4 Control Panel setup procedures allow you to custom-
ize the control panel to your needs and to the environment
in which it is installed. You can describe specific regulator
parameters and power-flow conditions, and define auto-
matic-mode operation. Previous generation controllers
used dip switch settings and jumpers for this purpose.
With the MJ-4 Control Panel, simply use front panel touch-
keys and the display screen to define the operating envi-
ronment. Also, the MJ-4 communication facilities in con-
junction with the MJXplorer software can be used to set
up the MJ-4 Control Panel.
The setup process for the MJ-4 Control Panel consists of
several steps:
Configuration
In this step, use the <CONFIGURE> Menu to describe
the regulator and the power distribution system. Use the
<ADV CONFIGURE> Menu to adjust optional or
advanced settings if desired.
Setpoints
In this step, use the <REGULATOR> Menu to define
Automatic Mode setpoints (voltage level, bandwidth, time
delay, etc.).
Logging Requirements
In this step, use the <LOG SETUP> Menu to define data
logging requirements (what values you want logged, how
often, under what conditions, etc.).
Security Definition
In this step, use the <PASSWORD> Menu to define pass-
words and to activate security protection.
Table 4.1
The <CONFIGURE> Menu
DATA ITEM
DESCRIPTION
TapChngr
Tap Changer Type
Type
Regulator type
Syst
System wiring configuration
DeltaPwr
Delta power configuration
Utility Pol
Utility winding polarity
Vprimary Max
Maximum primary voltage
U2 PT
Utility winding turns ratio
P2 PT
Potential Transformer turns ratio
CTratio
Current Transformer turns ratio
I FullLoad
Regulating Device Full Load Rating
PwrFlow
Power flow modes
Basis volts
Controller nominal voltage level
NeutOvRun
Neutral Over Run
Reset Min/Max?
Reset all min/max readings
Vers
Microprocessor software version
Memo1
User-supplied text
Memo2
User-supplied text
18
Communications Definition
In this step, use the <COMMUNICATIONS> Menu to
define communications parameters (baud rate, unit
address, etc.).
This chapter describes each of the setup parameters, and
explains how they are defined. The Communications Mod-
ule Instruction book contains additional detail and back-
ground information to help you make the proper
selections.
Note: Depending upon the version of software in
your MJ-4 Control Panel, your menus may be
slightly different than those described. If your
control panel does not support all of the fea-
tures described, please contact your Siemens
representative for details about obtaining the
latest version of the software.
VALID INPUTS
SIEMENS, GE, LTC, LTC.5, or COOP SD, DD, or QD
STRAIGHT or INVERTED
WYE, DELTA LAG, DELTA LEAD
OPEN or CLOSED
NORM, REV
65K (for regulators) or 650K (for LTC transformers)
1500 to 65,500:100 to 150
1500 to 65,500:100 to 150
50 to 7200:0.0 to 9.5
50 to 7200
F LOCK, R LOCK, IDLE R, BI-DIR, NEUT R, CO-GEN F LOCK
115, 120, or 125v
0.0 to 3.0 seconds
N or Y
NN.NNNN
Up to 10 Characters
Up to 10 Characters
DEFAULT
INC
SIEMENS
- - -
STRAIGHT
- - -
WYE
- - -
OPEN
- - -
NORM
- - -
65K
- - -
7200:120
1 Volt
7200:120
1 Volt
200:0.2
1:0.1
200
1 Amp
- - -
120
- - -
2.0
0.1 sec
N
- - -
- - -
- - -
Reg. Serial#
- - -
Tested by
- - -
Siemens Energy, Inc.