Siemens MJ-4A Installation And Operation Manual page 31

Voltage regulator control panel
Hide thumbs Also See for MJ-4A:
Table of Contents

Advertisement

4
Setting Up the MJ-4A & MJ-4B Control Panel
4.3.40 Current Bias
The user may choose None, Fwd, Rev or NeutT for current
flow modes. The Bias percent is selected from the follow-
ing Bias % data item.
4.3.41 Bias Percent
The minimum Bias percent is 0% and the maximum is
10%. The user may chose to use any value between the
maximum and minimum in increments of 1%. This func-
tionality is only in effect when the power flow mode is Bi-
Directional and Current Bias is not selected as "None" .
Note that, the Bias percent must be greater than the I
Threshold %. Typically, I Threhold % should be set to 0%.
For a detailed description, see Section 6.5.3
4.3.42 Remote Btn
The functionality of the Remote / Local button can be
enabled or disabled from this screen. When Enabled,
pressing the Remote/Local button will cause the control to
function as described in Section 6.1; when set to Dis-
abled, the control can enter the Manual, Off, or Auto-
Remote modes. The Auto-Local mode is disabled.
This Feature is not available in the MJ-4B Panel, if a user
attempts to change the setting on a MJ-4B, the display
would show "N/A IN MJ4B" .
Siemens Energy, Inc.
27