Siemens MJ-4A Installation And Operation Manual page 24

Voltage regulator control panel
Hide thumbs Also See for MJ-4A:
Table of Contents

Advertisement

4
Setting Up the MJ-4A & MJ-4B Control Panel
U2PT: 7620:121
P2PT: 7620:120
Figure 4.1 Typical Siemens Regulator Nameplate for older ANSI Type B (Inverted) Regulator
Note: Items are not highlighted on actual nameplate
U2PT: 7620:124
P2PT: 7620:124
Figure 4.2
Typical Siemens Regulator Nameplate for ANSI A (Straight) regulator without a Load Side PT.
20
SIEMENS
5/8% Step-Voltage Regulator
Single Phase Type JFR
60 Hz
76.2 kVA 7620 volts 10% in 32 - 5/8% Steps
Insulating Fluid :
ASTM D-3487 Type II Mineral Oil
Fluid PCB co ntent :
Less tha n 1 p pm at tim e of manufacture
Untanking Hgt
=
114 in.
Untanking Wgt =
937 lbs.
% Regulation
10
8
7
6
5
3/4
1/2
1/4
Max Amps
100
110
120
135
160
Forward Power Flow - Connect Load Side
Voltage Transformer per Table 1.
Control & M otor
Control Panel Conn
Load
Volts
Volts
Connect
PA
P14A
Control
10%
E-P2
*
to
to
8000
127 V
P2-P3
20
27
7620
121 V
P2-P3
20
21
7200
123 V
P2-P4
20
23
6930
118 V
P2-P4
23
21
5000
124 V
P2-P5
21
20
4330
125 V
P2-P6
20
20
2500
121 V
P2-P7
25
21
Reverse Power Flow - Connect Source Side
Voltage Transformer per Table 2.
Control & M otor
Control Panel Conn
Source
Volts
Volts
Connect
PB
P14B
Control
10%
E-P12
*
to
to
8000
120 V
P12-P13
20
20
120 V
P12-P14
7620
20
20
7200
120 V
P12-P15
20
20
Aluminum conductor in shunt winding.
Aluminum conductor in series winding.
Do not by-pass unless on neutral and control switch on panel is off
See instruction book before placing in service.
S i e m e n s P o w e r T r a n s m i s s i o n & D ist r i b u t i o n , I n c .
M a d e i n U S A
J a c k s o n , M S
Serial No.
55 C Rise
95 BIL
Class 0A
100 Amps
Oil
=
62 gals
Total Wgt
=
1598 lbs.
* Control diag :
Nameplate :
SOURCE
SL
LOAD
S
L
CT
Volts
E1
100 : 0.2
C3
E3
P14
120 V
P13
P15
AMPS
120 V
120 V
120 V
125 V
125 V
K
125 V
M
A
B
0
1 2 3 4 5 6
7 8
P6
P4
E2
Volts
P7
P5
P3
120 V
120 V
120 V
CT sec conn C2 to C3
21-115905-002
TapChngr SIEMENS
I FullLoad 100
CTratio 100:0.2
Tap Changer
Reversing Switch
Tap Changer
Preventive
Autotransformer
Utility Pol NORM
(E2 to right of P terminals)
TapChngr SIEMENS
I FullLoad 328
Type STRAIGHT
CTratio 400:0.2
Utility Pol NORM
(E2 to right of
U Terminals)
Siemens Energy, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mj-4b

Table of Contents