Appendix D: Menu Parameters
If the Un - - Ux taps are to the left of E2 with no taps to
the right of E2, and the polarity mark is on one of the
U taps, specify Utility Pol: NORM. (See Figure D.1.)
Single-Phase Straight Design - Taps to the
Figure D.1
Left of E2
If the Un - - Ux taps are to the right of the E2, and the
polarity mark is on the E2 tap, specify Utility Pol: REV. (See
Figure D.2.)
Figure D.2
Single-Phase Straight Design - Taps to the
Right of E2
Table D.3
Nameplate for Single-Phase Straight Regulator with Cooling Fan
Single Phase Straight Regulator with Cooling Fan
Load
Volt Tran
Control Panel P to
Volts
Sec Conn
P14 to
+/-10%
P2 to
14400
P3 - 120
20
13200
P4 - 120
20
7200
P5 - 120
20
From the table, the system load voltage is 7200 volts; therefore, U2 would be connected to U6. Now check the connection
diagram:
66
Basis
Aux Volts Motor
Volts
Conn U2 to Volts
20
120
U3
20
120
U4
20
120
U6
D.3.1.3 Single-Phase Straight design regulators
(ANSI type A) with forced air cooling
For these regulators, the Utility winding not only provides
power to the controller — it also provides power for the
forced air fan(s). The E2 tap is located between the Un - -
Ux terminals on the regulator's nameplate schematic. The
U5 tap is normally used for fan voltage and can be either
to the left or to the right of E2. To determine whether the
polarity is 'normal' or 'reverse' , you must examine both the
schematic diagram and the connection table on the name-
plate. From the connection table, determine the tap to
which U2 should be connected.
If the tap to which U2 is connected and the polarity
mark are to the left of E2 on the schematic, set Utility-
Pol:NORM.
If the tap to which U2 is connected is to the right of
E2 on the schematic, set UtilityPol:REV.
Examples
For both of the examples on the next page, use the
nameplate connection table shown in Table D.3:
Fan Connection
U21 to
126
U3
126
U53
126
U6
U15 to
Volts
U7
240
U7
242
U8
240