Technibel CHGF Series Technical Instructions page 11

Air to water heat pump and chiller
Table of Contents

Advertisement

5.1 - chGF capacities in cold mode (contd.)
• Tbs
Outside air temperature (dry bulb).
1
• Tw in / out Water inlet / outlet temperature.
• PF
Cooling capacity.
• Pa
Power consumption.
Tbs
1
en14511
Tw in Tw out
°c
°c
kW
10
5
60.77 14.49 4.19 58.17 15.69 3.71 55.17 16.99 3.25 52.17 18.59 2.81 48.97 20.29 2.41 45.57 22.19 2.05
11
6
62.67 14.59 4.30 59.87 15.79 3.79 56.97 17.19 3.31 53.67 18.69 2.87 50.47 20.39 2.48 46.87 22.39 2.09
12
7
64.47 14.69 4.39 61.67 15.89 3.88 58.57 17.29 3.39 55.37 18.79 2.95 51.87 20.49 2.53 48.27 22.39 2.16
13
8
66.47 14.69 4.52 63.47 15.99 3.97 60.27 17.39 3.47 57.07 18.89 3.02 53.47 20.69 2.58 49.77 22.59 2.20
chGF 55
14
9
68.47 14.79 4.63 65.27 16.09 4.06 62.07 17.49 3.55 58.67 18.99 3.09 55.07 20.79 2.65 51.17 22.69 2.26
15
10
70.37 14.89 4.73 67.07 16.19 4.14 63.97 17.59 3.64 60.27 19.09 3.16 56.67 20.89 2.71 52.67 22.79 2.31
16
11
72.17 15.09 4.78 69.07 16.29 4.24 65.67 17.69 3.71 61.97 19.19 3.23 58.17 20.99 2.77 54.27 22.89 2.37
17
12
74.47 15.19 4.90 71.07 16.39 4.34 67.47 17.79 3.79 63.67 19.39 3.28 59.87 21.09 2.84 55.77 22.99 2.43
10
5
78.13 18.04 4.33 74.53 19.74 3.78 70.93 21.64 3.28 66.63 23.74 2.81 62.24 26.24 2.37 57.44 29.04 1.98
11
6
80.33 18.14 4.43 76.73 19.84 3.87 72.93 21.74 3.35 68.73 23.94 2.87 64.03 26.34 2.43 59.14 29.14 2.03
12
7
82.53 18.34 4.50 79.03 20.04 3.94 74.93 21.84 3.43 70.63 24.04 2.94 65.93 26.44 2.49 60.94 29.24 2.08
13
8
85.13 18.44 4.62 81.23 20.14 4.03 77.13 22.04 3.50 72.63 24.14 3.01 67.83 26.64 2.55 62.64 29.34 2.13
chGF 70
14
9
87.43 18.64 4.69 83.43 20.24 4.12 79.33 22.14 3.58 74.53 24.34 3.06 69.63 26.74 2.60 64.33 29.54 2.18
15
10
89.82 18.74 4.79 86.03 20.44 4.21 81.53 22.34 3.65 76.73 24.44 3.14 71.63 26.84 2.67 66.03 29.64 2.23
16
11
92.62 18.94 4.89 88.33 20.64 4.28 83.63 22.54 3.71 78.93 24.64 3.20 73.63 27.04 2.72 68.03 29.84 2.28
17
12
95.02 19.04 4.99 90.62 20.74 4.37 86.03 22.64 3.80 81.03 24.74 3.28 75.63 27.24 2.78 69.93 29.94 2.34
10
5
85.64 20.92 4.09 81.64 22.82 3.58 77.04 25.12 3.07 72.54 27.62 2.63 67.54 30.42 2.22 62.24 33.72 1.85
11
6
88.34 21.02 4.20 83.94 23.02 3.65 79.54 25.22 3.15 74.74 27.72 2.70 69.64 30.62 2.27 64.14 33.82 1.90
12
7
90.84 21.12 4.30 86.34 23.12 3.73 81.84 25.32 3.23 76.94 27.92 2.76 71.74 30.72 2.34 66.04 33.92 1.95
13
8
93.24 21.32 4.37 89.04 23.32 3.82 84.14 25.52 3.30 79.14 28.02 2.82 73.84 30.82 2.40 67.94 34.02 2.00
chGF 76
14
9
96.24 21.42 4.49 91.44 23.42 3.90 86.74 25.72 3.37 81.24 28.22 2.88 75.84 31.02 2.44 69.94 34.12 2.05
15
10
98.84 21.52 4.59 93.84 23.62 3.97 89.14 25.82 3.45 83.74 28.32 2.96 77.94 31.22 2.50 72.04 34.22 2.11
16
11
101.44
17
12
104.54
20°c
25°c
PF
Pa
err
PF
Pa
kW
kW
kW
21.72 4.67 96.94 23.72 4.09 91.44 26.02 3.51 86.24 28.52 3.02 80.24 31.32 2.56 74.04 34.32 2.16
21.92 4.77 99.44 23.92 4.16 93.94 26.12 3.60 88.44 28.72 3.08 82.44 31.62 2.61 76.24 34.52 2.21
30°c
err
PF
Pa
err
PF
kW
kW
kW
11
35°c
40°c
Pa
err
PF
Pa
err
kW
kW
kW
45°c
PF
Pa
err
kW
kW

Hide quick links: