Technibel PHRT 9 Installation Instruction

Technibel PHRT 9 Installation Instruction

Heat pump with hydraulic equipment
Hide thumbs Also See for PHRT 9:

Advertisement

F
NOTICE D'INSTALLATION
GB
INSTALLATION INSTRUCTION
I
MANUALE D'INSTALLAZIONE
(Etiquette plaque signalétique)
MANUAL DE INSTALACIÓN
E
D
AUFSTELLUNGSHANDBUCH
PHRT 9 / 18
PHRT 12
PHRT 16
PHRT 18
PHRT 9
Pompe à chaleur avec équipement hydraulique - Fluide réfrigérant R 410 A
Heat pump with hydraulic equipment - R 410 A refrigerant
Refrigeratore d'acqua in versione pompa di calore con sezione idronica incorporata
Fluido refrigerante R 410 A
Bomba de calor con equipamiento hidráulico - Fluido refrigerante R 410 A
Wärmepumpe mit Hydraulikmodul Kältemittel R 410 A
Avril 2006
10 11 474 - F.GB.I.E.D - 00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PHRT 9 and is the answer not in the manual?

Questions and answers

Summary of Contents for Technibel PHRT 9

  • Page 1 NOTICE D’INSTALLATION INSTALLATION INSTRUCTION MANUALE D’INSTALLAZIONE (Etiquette plaque signalétique) MANUAL DE INSTALACIÓN AUFSTELLUNGSHANDBUCH PHRT 9 / 18 PHRT 12 PHRT 16 PHRT 18 PHRT 9 Pompe à chaleur avec équipement hydraulique - Fluide réfrigérant R 410 A Heat pump with hydraulic equipment - R 410 A refrigerant Refrigeratore d’acqua in versione pompa di calore con sezione idronica incorporata...
  • Page 2: Table Of Contents

    MARKING This product marked conforms to the essential requirements of the Directives: - Low voltage no. 73/23 EEC, modified 93/68 EEC. - Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 and 93/68 EEC. SUMMARY 1 - Generalities ........2 2 - Presentation .
  • Page 3: Presentation

    14 - Filling / drainage of the water circuit. - Plastic grille. 7 - Microprocessor control unit display 15 - Air vent. keyboard. 16 - Hole for connecting cables. 8 - Circulating pump. PHRT 9 PHRT 12 PHRT 16 PHRT 18...
  • Page 4 2.2 - DIMENSIONS AND WEIGHT Weight (kg) PHRT 9 Water inlet connection 3/4" (male) with air vent valve Water outlet connection 3/4" (male) Water circuit fill/drain - 1/2" male Holes for electric cables 1190 Weight (kg) PHRT 12 PHRT 16 PHRT 18 Water inlet connection 1"...
  • Page 5: Installation

    - use the anti-vibration mountings supplied, making sure that they are not A (m) compressed too much when the fastening screws are tightened, - the blown air must not be directed towards surrounding windows, PHRT 9 0.15 - vibrations and noise must not be transmitted to a nearby building, PHRT 12/16/18 0.25...
  • Page 6 (to neutral) as per NF C 15-100. POWER SUPPLY CABLE • Section 230V/1/50Hz : 3 G 4 mm for PHRT 9 and PHRT 12. • Section 400V/3N/50Hz : 5 G 2.5 mm for PHRT 12, 16 and 5 G 4 mm for PHRT 18.
  • Page 7: Operation Of "Ech" Electronic Control

    4.3.4 - REMOTE CONTROL • See paragraph "accessories". 4.3.5 - MISCELLANEOUS • Alarm transfer: Potential-free changeover contact (2A - 250 VAC max.) available on the unit's terminal strip (terminals 5 (common), 6 and 7 of the printed circuit) for remote signaling. See schematic. - In case of alarm : - contact open between terminals 5 and 6, - contact closed between terminals 5 and 7.
  • Page 8 5.3.2 - CTN TYPE TEMPERATURE PROBE Temperature (°C) Ohmic value (Ohm) • 10 kΩ at 25° C. 67 740 42 450 27 280 17 960 12 090 10 000 8 313 5 820 4 161 3 021 2 229 5.4 - OPERATING MODES •...
  • Page 9 5.6 - PARAMETERS - DISPLAYING AND ADJUSTING 5.6.1 - GENERAL • Parameter access is structured within a multi-level menu, see the diagram below. Simultaneously pressing the "ON/OFF" (1) and "Mode" (2) buttons for a brief moment (less than 2 seconds) gives access to the next level. Simultaneously pressing for a long moment (longer than 2 seconds) turns you to the previous level.
  • Page 10 For terminal unit and boiler overhaul applications, the configuration and parameterisation of each machine are factory-set for optimum operation. Settings for terminal units and Adjustment range boiler overhaul applications Code Parameters PHRT 9/12/16 PHRT 18 PHRT 9/12/16 PHRT 18 Heating set point 48° C 45° C 20 to 50°...
  • Page 11 SUMMARY TABLE OF ALARMS Compressor Alarm Code Inhibition delay Fan stop Pump stop Remarks stop Fault on probe 1 Fault on probe 2 Fault on probe 3 Fault on probe 4 H.P. B.P. (low pressure) 30'' at start-up From probe Anti-freeze (water 60'' SD2 (water outlet).
  • Page 12 • Condensate tank heating cord control: (Accessory, see installation in paragraph 6.2). - actuated if the outside temperature (probe SD4) drops below 0°C (regardless the unit's operating mode). The "heating element" indicator light (8) illuminates. • Operating mode selection: - the controller is factory configured to control the unit by 3 outside contacts: •...
  • Page 13: Accessories

    6 - ACCESSORIES 6.1 - WATER CONNECTION HOSES • Length 1 m, insulated, female: - Ø 3/4” code 70600054 for PHRT 9, - Ø 1” code 70600055 for PHRT 12, 16 and 18. 6.2 - CONDENSATE TANK HEATING CORD KIT •...
  • Page 14 • This kit is used to lower the start-up current of the single-phase compressors. The average RMS current during the start-up phase is approximately 42 A for the PHRT 9 and approximately 43 A for the PHRT 12 (single-phase). • After having removed the side panel, also remove the upper panel A.
  • Page 15: Starting

    6.5 - RS 485 COMMUNICATION INTERFACE (MODBUS protocol) • Code 70250056. • After removing the side panel, also remove the front panel A (remove the three retaining screws B and pull the panel downwards). • Secure the communication interface C on the left-hand side of the electric panel. •...
  • Page 16: Maintenance Instruction

    TECHNIBEL proposes a wide range of perfectly adapted professional cleaning, maintenance and repair products for complete and efficient maintenance. For an optimum result, TECHNIBEL air-conditioners must be maintained with TECHNIBEL maintenance products.
  • Page 17: Circulator Curves

    10 - CIRCULATOR CURVES CIRCULATOR SXM 32 - 55 CIRCULATOR UPS 25 - 125 PHRT 9 PHRT 12 Speed 3 Speed 3 Speed 2 Speed 2 Speed 1 Speed 1 Water flowrate (m Water flowrate (m CIRCULATOR SXM 32 - 80...
  • Page 18: Pressure Curves

    11 - PRESSURE CURVES 11.1 - HEATING MODE LOW PRESSURE HIGH PRESSURE PHRT 9 50° C Water outlet temperature Water outlet temperature 50° C 45° C 45° C 35° C 35° C -10 -8 -6 -4 -2 0 8 10 12 14 16 18...
  • Page 19 11.2 - COOLING MODE LOW PRESSURE HIGH PRESSURE PHRT 9 43° C Outside temperature 35° C Outside temperature 35° C 25° C 43° C 25° C 9 10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20 Water outlet temperature (°C)
  • Page 20: Wiring Diagrams

    White Electrovalve Condensation or defrosting temperature probe Water differential pressure switch Outside air probe Phase-sequence controller Contactor compressor ELECTRICAL DIAGRAM - PHRT 9 - 230/1/50 10 05 793 - 01 Filter Controller Interface panel Alarm Compressor Circulating pump ELECTRICAL DIAGRAM - PHRT 12 - 230/1/50...
  • Page 21 ELECTRICAL DIAGRAM - PHRT 12/16 - 400/3N/50 10 05 816 - 00 Controller Filter Interface panel Alarm Fan 1 Fan 2 Compressor Circulator ELECTRICAL DIAGRAM - PHRT 18 - 400/3N/50 10 05 796 - 01 Controller Filter Interface panel Alarm Fan 1 Fan 2 Compressor...
  • Page 22 Par souci d'amélioration constante, nos produits peuvent être modifiés sans préavis. Due to our policy of continuous development, our products are liable to modification without notice. Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preaviso. En el interés de mejoras constantes, nuestros productos pueden modificarse sin aviso prévio.

This manual is also suitable for:

Phrt 12Phrt 16Phrt 18

Table of Contents