- The charge must be undertaken in liquid phase. - Use a balance and a dip pipe type R 410 A cylinder. 1 - aPPlIcaTIon - usE • Hot water generator for residential heating exclusively in the scope of Technibel systems.
Minimum: 1.5 bar. Maximum: 2.5 bar. Available pressure: See paragraph 8. Sound level: See paragraph 9. 3.1 - sInGlE-PHasE modEls model PHRIE 095 PHRIE 125 PHRIE 155 PHRIE 175 PHRIE 195 PHIE 095 PHIE 125 PHIE 155 Main power supply...
PHRIE 095 PHRIE 125 PHRIE 155 PHRIE 175 PHRIE 195 PHIE 095 PHIE 125 PHIE 155 Main power supply V/PH/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Total maximum power consumption With 4.5 kW support electric heater 7.07 7.65 With 3 kW support electric heater 5.57...
model PHRIE 157 PHRIE 177 PHRIE 197 PHRIE 257 PHRIE 307 PHIE 157 Main power supply V/PH/Hz 400/3N/50 400/3N/50 400/3N/50 400/3N/50 400/3N/50 Total maximum power consumption With 9 kW support electric heater 16.40 17.50 With 6 kW support electric heater 10.20 10.80 12.50...
• Devices reduce or prohibit operation of the appliance outside these limits. - HEaTInG modE oPERaTInG lImITs: Water output Water output temperature (°C) temperature (°C) PHRIE 095 PHIE 095 PHRIE 125 PHIE 125 Outdoor air dry bulb Outdoor air dry bulb temperature (°C)
6 - PowER TablEs 6.1 - HEaTInG caPacITIEs note: the heating capacities are those of the heat pump, without the electric heater. PHRIE 095 PHIE 095 maximum heating capacity (kw) maximum input power (kw) water outlet temperature (°c) water outlet temperature (°c) 2.19...
6.2 - coolInG caPacITIEs PHRIE 095 PHRIE 125 maximum cooling maximum input maximum cooling maximum input capacity (kw) power (kw) capacity (kw) power (kw) water outlet water outlet water outlet water outlet temperature temperature temperature temperature (°c) (°c) (°c) (°c) 2.98...
PHRIE 155 PHRIE 195 PHRIE 157 PHRIE 197 maximum cooling maximum input maximum cooling maximum input capacity (kw) power (kw) capacity (kw) power (kw) water outlet water outlet water outlet water outlet temperature temperature temperature temperature (°c) (°c) (°c) (°c) 4.38 5.25 0.99...
Page 24
PHRIE 257 PHRIE 307 maximum cooling maximum input maximum cooling maximum input capacity (kw) power (kw) capacity (kw) power (kw) water outlet water outlet water outlet water outlet temperature temperature temperature temperature (°c) (°c) (°c) (°c)
8 - cuRvEs oF avaIlablE PREssuREs (unit outlet) • These available pressures are indicated for the water flow to be adjusted at the installation, according to the maximum water outlet temperature which is determined according to the application. PHRIE 095 PHIE 095 water flow (m 0.67 nominal at water...
Page 26
PHRIE 125 PHIE 125 water flow (m 0.82 nominal at water 1.40 nominal at water 1.45 nominal at water 1.90 nominal at water outlet temperature 55°C outlet temperature 45°C outlet temperature 35°C outlet temperature 25°C PHRIE 155 PHIE 155 PHRIE 157 PHIE 157 water flow (m 1.03 nominal at water outlet...
Page 27
PHRIE 195 PHRIE 197 water flow 1.30 nominal at water outlet 2.52 nominal at water 2.59 nominal at water 3.20 nominal at water temperature 55°C outlet temperature 45°C outlet temperature 35°C outlet temperature 25°C PHRIE 257 water flow (m 2.00 nominal at water 3.35 nominal at water 3.51 nominal at water 4.20 nominal at water...
11 - ElEcTRonIc conTRol It features 2 parts: - Monitoring / control assembly with INVERTER technology, for the thermodynamic device. Built into the heat pump, it controls: - The variable-speed compressor. - The variable-speed fan. - The electronic expansion valve and the cycle inversion valve. - The water circulating pump (with frost protection and anti-sticking functions).
Page 30