Common specifications
 Single-phase 100V power supply
Model FR-D710W-K
Applicable motor capacity (kW)
Rated capacity (kVA)

Rated current (A)
Overload current rating

Rated voltage
Regenerative braking torque
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (kVA)
Protective structure (JEM1030)
Cooling system
Approximate mass (kg)

The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.

The rated output capacity assumes the following output voltages: 230V for three-phase 200V/single-phase 200V/single-phase 100V, and 440V for three-
phase 400V.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about

The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large.
(Option brake resistor cannot be used for 0.1K and 0.2K.) A brake unit (FR-BU2) may also be used.

The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).

For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.

In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-
phase input model. Use the motor with less load so that the output current is within the rated motor current range.
10.2 Common specifications
Control method
Output frequency range
Analog input
Frequency setting
resolution
Digital input
Analog input
Frequency
accuracy
Digital input
Voltage/frequency characteristics
Starting torque
Torque boost
Acceleration/deceleration time setting
DC injection brake
Stall prevention operation level
Surrounding air temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude/vibration

When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed closely attached (0cm clearance).

Temperatures applicable for a short time, e.g. in transit.
44
0.1
0.2
0.1
0.2

0.3
0.6
0.8
1.4
150% 60s, 200% 0.5s
(inverse-time characteristics)
Three-phase 200 to 230V
150%

Single-phase 100 to 115V 50Hz/60Hz
90 to 132V 50Hz/60Hz
0.5
0.9

Enclosed type (IP20)
Natural
0.6
0.7
Soft-PWM control/high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control,
and Optimum excitation control are available)
0.2 to 400Hz
0.06Hz/60Hz (terminal 2, 4: 0 to 10V/10bit)
0.12Hz/60Hz (terminal 2, 4: 0 to 5V/9bit)
0.06Hz/60Hz (terminal 4: 0 to 20mA/10bit)
0.01Hz
Within 1% of the maximum output frequency (25°C 10°C)
Within 0.01% of the set output frequency
Base frequency can be set from 0 to 400Hz. Constant-torque/variable torque pattern can be selected
150% or more (at 1Hz)...when General-purpose magnetic flux vector control and slip compensation is set
Manual torque boost
0.1 to 3600s (acceleration and deceleration can be set individually),
Linear and S-pattern acceleration/deceleration modes are available.
Operation frequency (0 to 120Hz), operation time (0 to 10s), and operation voltage (0 to 30%) can be changed
Operation current level (0 to 200%), and whether to use the function or not can be selected
-10°C to +50°C maximum (non-freezing) 
90%RH or less (non-condensing)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Maximum 1000m, 5.9m/s
0.4
0.75
0.4
0.75
1.0
1.7
2.5
4.2

100%
±5%
1.5
2.5
0.9
1.4
2
that of the power supply.
2
or less at 10 to 55Hz (directions of X, Y, Z axes)