2.2
Installation of the inverters and precautions
(1) Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to mount the inverter to the surface. (Remove the covers in the directions of the
arrows.)
FR-D720-0.1K to 0.75K
FR-D720S-0.1K to 0.75K
FR-D710W-0.1K to 0.4K
Front cover
NOTE
When encasing multiple inverters, install them in parallel as a cooling
measure.
Install the inverter vertically.
For heat dissipation and maintenance, allow minimum clearance shown
in the figures below from the inverter to the other devices and to the
inner surface of the enclosure.
5cm
5cm
Measurement
position
-10 C to +50 C
(non-freezing)

Allow 5cm or more clearance for 5.5K or higher.

When using the inverters at the surrounding air temperature of 40C or less, the inverters can be installed without any clearance between
them (0cm clearance).
(2) Environment
Before installation, check that the environment meets the specifications on page 44.
Note
 Install the inverter on a strong surface securely and vertically with bolts.
 Leave enough clearances and take cooling measures.
 Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
 Install the inverter on a nonflammable wall surface.
 When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat
generation of the contained devices and the operating environment.
Installation of the inverters and precautions
FR-D720-1.5K to 3.7K
FR-D740-0.4K to 3.7K
FR-D720S-1.5K, 2.2K
FR-D710W-0.75K
Front cover
Wiring cover
Measurement
10cm or more
position
5cm
1cm or
1cm or
more
more
∗1, ∗2
10cm or more
FR-D720-5.5K to 15K
FR-D740-5.5K to 15K
Front cover
Wiring cover
1cm or
∗1, ∗2
more
∗1
2
7