Start/stop from the operation panel (PU operation)
5.1.4
Setting the frequency by analog input (voltage input/current input)
POINT
 Use the operation panel (
 Use the potentiometer (frequency setting potentiometer) (voltage input) or 4-to-20mA input (current input) to
give a frequency command.
 Set "4" (External/PU combined operation mode 2) in Pr. 79 Operation mode selection.
[Connection example for voltage input]
(The inverter supplies 5V power to the frequency setting
potentiometer. (terminal 10))
Frequency
setting
potentiometer
Operation example
Operate at 60Hz.
Screen at power-ON
1.
The monitor display appears.
Assignment of the AU signal (current input) (Refer to the step 3 for voltage input.)
Set Pr. 160 to "0" to activate extended parameters.
2.
To assign the AU signal, set "4" in one of Pr. 178 to Pr. 182. (Refer to page 4 to change the setting.)
Turn ON the AU signal.
Easy operation mode setting
3.
Press
and
Operation mode selection
4.
Turn
until "
Operation mode setting
5.
Press
to enter the setting. (Set "4" in Pr.79.)
"
" and "
Start
6.
Press
. [RUN] blinks fast as no frequency command is given.
Acceleration  constant speed
For voltage input, turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
7.
For current input, input 20mA.
The frequency value on the display increases in Pr. 7 Acceleration time, and "
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
Deceleration
For voltage input, turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full.
8.
For current input, input 4mA.
The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor stops rotating with "
[RUN] blinks fast.
Stop
9.
Press
. [RUN] indicator turns OFF.
REMARKS
 For voltage input, the frequency (maximum potentiometer setting) at the full right turn of the (frequency setting) potentiometer is
60Hz in the initial setting. (To change the setting, use Pr. 125.) (Refer to page 30.)
 To input 10VDC to terminal 2, set Pr. 73 Analog input selection = "0". The initial value is "1 (0 to 5V input)" (
of the Instruction Manual (Applied.)).
 For current input, the frequency at 20mA input is 60Hz in the initial setting. (To change the setting, use Pr. 126.) (
Chapter 4 of the Instruction Manual (Applied.))
 When terminal 10 is used, the maximum output frequency may fluctuate in a range of 2 to 3Hz due to fluctuations in the output
voltage (5V  0.2VDC). Use Pr. 125 or C4 to adjust the output frequency at the maximum analog input as required. (
Chapter 4 of the Instruction Manual (Applied).)
26
) to give a start command.
Inverter
Operation
panel
10
2
5
for 0.5s. "
" appears, and the [PRM] indicator blinks.
" appears. [PU] and [PRM] indicators blink.
" appear alternately. [PU] and [EXT] indicators are lit.
[Connection example for current input]
Assign the AU signal in one of Pr. 178 to Pr. 182.
AU signal
Current signal
source
(4 to 20mADC)
Operation
" (60.00Hz) appears.
Inverter
AU signal
Operation
panel
(terminal RH)
SD
4(+)
5(-)
" (0.00Hz) displayed.
Refer to Chapter 4
Refer to
Refer to