Wiring
2.3.5
Assigning signals (output stop signal (MRS), reset signal (RES), etc.) to contact
input terminals
POINT
Use Pr.178 to Pr.182 (input terminal function selection) to select and change the functions assigned to input
terminals.
To assign the output stop signal (MRS) to the terminal RH, for example, assign "24" to Pr.182 RH terminal
function selection. (Refer to page 4 to change a parameter setting value.)
Pr.
Name
178
STF terminal function selection
179
STR terminal function selection
180
RL terminal function selection
181
RM terminal function selection
182
RH terminal function selection
NOTE
Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
16
Initial
Value
0: Low-speed operation command (RL)
60
1: Middle-speed operation command (RM)
2: High-speed operation command (RH)
3: Second function selection (RT)
61
4: Terminal 4 input selection (AU)
5: JOG operation selection (JOG)
0
7: External thermal relay input (OH)
8: Fifteen speed selection (REX)
10: Inverter operation enable signal (X10)
1
(FR-HC2/FR-CV connection)
12: PU operation external interlock (X12)
14: PID control valid terminal (X14)
2
16: PU-External operation switchover (X16)
Range
18: V/F switchover (X18)
24: Output stop (MRS)
25: Start self-holding selection (STOP)
60: Forward rotation (STF)
61: Reverse rotation (STR)
62: Inverter reset (RES)
65: PU-NET operation switchover (X65)
66: External-NET operation switchover
(X66)
67: Command source switchover (X67)
9999: No function
Assigned to STF terminal (Pr. 178) only
Assigned to STR terminal (Pr. 179) only