Parameter
Hardware interrupt: Zero
crossing
1
Hardware interrupt: Com-
parison event for DQ0 oc-
curred
1
Hardware interrupt: Com-
parison event for DQ1 oc-
curred
1
Signal type
Signal evaluation
for counter inputs
Filter frequency
for counter inputs
1
Invert direction
1
(counter inputs)
Reaction to signal N
1
Frequency of
synchronization
1
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)
Manual, 06/2018, A5E03982218-AB
Value range
Deactivated
Activated
Deactivated
Activated
Deactivated
Activated
Pulse (A)
Pulse (A) and direction (B)
Count up (A), count down (B)
Incremental encoder (A, B
phase-shifted)
Incremental encoder (A, B, N)
Single
Double
Quadruple
100 Hz
200 Hz
500 Hz
1 kHz
2 kHz
5 kHz
10 kHz
20 kHz
50 kHz
100 kHz
200 kHz
500 kHz
1 MHz
Deactivated
Activated
No reaction to signal N
Synchronization at signal N
Capture at signal N
Once
Periodic
4.3 Manual operation (without technology object)
Default setting
Parameter
reassign-
ment in RUN
Deactivated
Yes
Deactivated
Yes
Deactivated
Yes
Pulse (A) and direc-
Yes
tion (B)
Single
Yes
200 kHz
Yes
Deactivated
Yes
No reaction to sig-
Yes
nal N
Once
Yes
Configuring/address space
Scope
HSP for STEP 7
(TIA Portal);
GSD file
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et-200mp

Table of Contents