Parameter data record
B.2 Parameter validation error
Error code in STATUS parame-
ter (hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
E1
2D
DF
80
E1
2E
DF
80
E1
2F
DF
80
E1
30
DF
80
E1
31
DF
80
E1
32
DF
80
E1
33
DF
80
E1
34
DF
80
E1
35
DF
80
E1
F0
Only for "Position input for "Motion Control"" technology object" operating mode
1
Only for DQn.1 functions "Between comparison value 0 and 1" and "Not between comparison value 0 and 1"
2
104
Meaning
"Between comparison value 0 and 1" con-
figured for DQn.0
"Not between comparison value 0 and 1"
configured for DQn.0
"Between comparison value 0 and 1" con-
figured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Not between comparison value 0 and 1"
configured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Capture" configured for DIn.m in "Measuring"
operating mode
"Set function of DI" parameter invalid
"Monoflop time" parameter invalid
"Transmission rate" parameter invalid
"Parity" parameter invalid
"Frame length" parameter invalid
Bit number LSB of the position value < 0
Bit number LSB of the position value > Bit
number MSB of the position value
(Bit number MSB of the position value) ‒
(Bit number LSB of the position value)
>= 31
Bit number MSB of the position value >
Frame length
"0" configured for "Pulse duration" parameter
Reserved bit is not set to 0.
Remedy
Configure "Between comparison value 0 and 1"
only for DQn.1
"Not between comparison value 0 and 1" config-
ured only for DQn.1
Only configure "Between comparison value 0 and
1" for DQn.1 when "Use by user program" is con-
figured for DQn.0
Only configure "Not between comparison value 0
and 1" for DQn.1 when "Use by user program" is
configured for DQn.0
Do not configure "Capture" for DIn.m in "Measuring"
operating mode.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Bit number LSB of the position value >= 0
Bit number LSB of the position value < Bit number
MSB of the position value
(Bit number MSB of the position value) ‒ (Bit
number LSB of the position value) < 32
Bit number MSB of the position value <= Frame
length
Enter valid parameter value.
Set reserved bit to 0.
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)