Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
USI structure = W#16#0007
Table 5- 12
USI structure = W#16#0007
Data block name
USI
Followed by the slot for the I/O module:
Slot
If slot 0 is specified, check the width of the station configuration (maximum 1 m).
Followed by 2 reserved bytes:
Reserved
Reserved
5.3.4

Invalid configuration states of the ET 200SP on PROFINET IO

Invalid configuration states
The following invalid configuration states of the ET 200SP distributed I/O system lead to the
failure of the IO device or prevent data exchange:
● Number of modules exceeds maximum configuration.
● Faulty backplane bus (e.g. defective BaseUnit). ET 200SP backplane bus interruptions do
not trigger an interrupt.
● At least one I/O module is plugged into a different BaseUnit as the one configured in the
parameters.
● No server module.
● Invalid or incorrectly configured BusAdapter.
Note
Removal of the server module will trigger a station stop. All I/O modules of the ET 200SP
distributed I/O system fail (substitute value behavior) but the interface module continues to
exchange data.
Revoking the station stop (by correcting the invalid configuration state) leads to a brief failure
of the ET 200SP distributed I/O system and automatic restart.
46
Content
Comment
W#16#0007
Manufacturer-specific diagnostics if operation is not possi-
ble with existing bus configuration
Result: Station stop
W#16#0001 to
Bit 8 to 15
W#16#0040
Bit 0 to 7
The I/O modules fail → substitute value behavior
The interface module continues to exchange data with
the IO controller
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)