Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF Manual page 45

Interface module
Hide thumbs Also See for SIMATIC ET 200SP IM 155-6 PN/2 HF:
Table of Contents

Advertisement

Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
Structure of the manufacturer-specific diagnostics data records (IM 155-6 PN HF Version < V3.3)
The structure of the diagnostics data records is differentiated by the BlockVersion. The
following BlockVersion applies to the IM 155-6 PN HF interface modules:
Table 5- 7
IM 155-6 PN HF interface module
6ES7155-6AU00-0CN0
Note
Manufacturer-specific diagnostics are not reported as of version V3.3 for the interface
module IM 155-6 PN HF.
Manufacturer-specific diagnostics in the User Structure Identifier (USI)
The following manufacturer-specific diagnostics are signaled in the USI with the
IM 155-6 PN HF interface module:
Table 5- 8
Manufacturer-specific diagnostics in the USI
USI no. W#16#...
0003
0004
0006
0007
USI structure = W#16#0003
Table 5- 9
USI structure = W#16#0003
Data block name
USI
Followed by the slot as of which the supply voltage L+ has failed.
Slot
Followed by 2 reserved bytes:
Reserved
Reserved
44
Structure of the manufacturer-specific diagnostics data records
Diagnostics
Group diagnostics: Missing supply voltage L+ for the potential groups
Diagnostics with missing server module
Diagnostics with incorrect BaseUnit
Diagnostics with incorrect bus configuration
Content
W#16#0003
W#16#0001 to
W#16#0040
BlockVersion
W#16#0101
Comment
Manufacturer-specific diagnostics with failure of supply
voltage L+ as of slot x of the ET 200SP module
Bit 8 to 15
Bit 0 to 7
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Bytes
2
1
1
1
1
Manual, 10/2018, A5E03915895-AH