Using The Compare Function (Model 1507) - Fluke 1507 User Manual

Insulation testers
Table of Contents

Advertisement

1507
INSULATION TESTER
Figure 8. Measuring Polarization Index and Dielectric
Absorption Ratios
Shop for Fluke products online at:
or
bbw10f.emf
MyFlukeStore
www.

Using the Compare Function (Model 1507)

Using the Compare Function (Model
1507)
Use the Compare function to set a pass/fail compare level
for the insulation measurements. To use the Compare
function:
1.
Press the  button to select the desired compare
value. You can choose from 100 kΩ, 200 kΩ, 500 kΩ,
1 MΩ, 2 MΩ, 5 MΩ, 10 MΩ, 20 MΩ, 50 MΩ, 100 MΩ,
200 MΩ, and 500 MΩ.
2.
Perform insulation tests as described earlier in this
manual.
3.
The green pass indicator will appear if the measured
value is greater than the selected value.
4.
Press and hold the  button for 1 second to
disable the Compare function. The pass indicator will
turn off when you start a new test or choose a new
compare value.
1.800.561.8187