8
TROUBLE SHOOTING
Problem
1
Operating temperature too high for selected
fittings
Actuator or
stem moves
2
Inadequate air supply
stiffly
3
Positioner defect
1
Bonnet is loose
2
Worn or damaged plug
3
Gaskets damaged
Excessive
4
Inadequate actuator thrust
leakage
5
Plug incorrectly adjusted
6
Incorrect direction of flow
7
Handwheel incorrectly adjusted (acts as an
end-stop)
1
Plug incorrectly adjusted (short stroke
Inadequate flow
2
Positioner defect
3
Operating requirements too high
1
Plug adjustment incorrect
2
Inadequate supply pressure
Plug slams
3
Trim too large for flow rate
Possible cause
Kämmer Series 341000 FCD KMENIM4104-01 03/18
1
Note the operating data and contact Flowserve
2
Check system for leaks in air supply or signal lines, re
tighten connections or replace lines if necessary
3
See operating instructions for positioner
1
See step 3.2.3 for re-tightening the bonnet correctly
2
Rework or replace plug
3
Renew gaskets
4
Check air feed. If air feed is OK, contact Flowserve
5
Correctly adjust plug according to step 3.3.1
6
Check specification. Contact Flowserve
7
Adjust handwheel
1
Correctly adjust plug according to step 3.3.1
2
See operating instructions for positioner
3
Check operating data. Contact Flowserve
1
Correctly adjust plug according to step 3.3.1
2
Check air supply, seal leaks, remove blockages
3
Replace trim
Remedy