Advanced Motor Protection and RTD Protection Functions
6.16 Device 49RTD - Machine Thermal Overload - Fixed Pickup RTD Protection
Picklist
RTD 11 Usage
RTD 11 Bearing, Ambient, etc.
RTD 11 Output Type
RTD 11 Output Type Alarm, Fault, etc.
RTD 11 Failure Response
RTD 11 Response to a shorted or open RTD
RTD 12 Menu (7508)
Keypad Parameter Text
Tool Parameter Help Text
RTD 12 Pickup Level
RTD 12 Pickup Level
RTD 12 Dropout Level
RTD 12 Percentage under Pickup Level for Reset
RTD 12 Pickup Delay
RTD 12 Pickup Delay
RTD 12 Dropout Delay
RTD 12 Time to Reset
Picklist
RTD 12 Usage
RTD 12 Bearing, Ambient, etc.
RTD 12 Output Type
RTD 12 Output Type Alarm, Fault, etc.
RTD 12 Failure Response
RTD 12 Response to a shorted or open RTD
78
ID
Units
Default
Value
7502
None
7507
Disabled
7722
Alarm
ID
Units
Default
Value
7510
150 °C
● °C
● °F
7511
%
7512
sec
7513
sec
ID
Units
Default
Value
7509
None
7514
Disabled
7723
Alarm
Advanced Motor Protection for Variable Speed Operation
Values
● Ambient
● Stator
● Bearing
● Other
● None
● Disabled
● Alarm
● LatchedAlarm
● Trip
● Block Start
● Alarm
● Trip
Minimum - Maximum Val‐
ue
0 - 572
2
0 -50
10
0 -180
5
0 - 180
Values
● Ambient
● Stator
● Bearing
● Other
● None
● Disabled
● Alarm
● LatchedAlarm
● Trip
● Block Start
● Alarm
● Trip