Advanced Motor Protection and RTD Protection Functions
6.3 Device 12 - Variable Pickup Overspeed
OverSpeed Curve Menu (7190)
Keypad Parameter Text
Tool Parameter Help Text
0% Speed Pickup
Define Pickup Level in %Speed at 10% Demanded
Speed
10% Speed Pickup
Define Pickup Level in %Speed at 20% Demanded
Speed
20% Speed Pickup
Define Pickup Level in %Speed at 30% Demanded
Speed
30% Speed Pickup
Define Pickup Level in %Speed 40% Demanded
Speed
40% Speed Pickup
Define Pickup Level in %Speed at 50% Demanded
Speed
50% Speed Pickup
Define Pickup Level in %Speed at 60% Demanded
Speed
60% Speed Pickup
Define Pickup Level in %Speed at 70% Demanded
Speed
70% Speed Pickup
Define Pickup Level in %Speed at 80% Demanded
Speed
80% Speed Pickup
Define Pickup Level in %Speed at 90% Demanded
Speed
90% Speed Pickup
Define Pickup Level in %Speed at 100% Demanded
Speed
100% Speed Pickup
Define Pickup Level in %Speed at 110% Demanded
Speed
110% Speed Pickup
Define Pickup Level in %Speed at-120% Demanded
Speed
120% Speed Pickup
Define Pickup Level in %Speed at 130% Demanded
Speed
130% Speed Pickup
Define Pickup Level in %Speed at 140% Demanded
Speed
34
ID
Units
Default
7191
%
7192
%
7193
%
7194
%
7195
%
7196
%
7197
%
7198
%
7199
%
7200
%
7201
%
7202
%
7203
%
7204
%
Advanced Motor Protection for Variable Speed Operation
Minimum - Maximum Value
Value
10
0 - 250
20
0 - 250
30
0 - 250
40
0 - 250
50
0 - 250
60
0 - 250
70
0 - 250
80
0 - 250
90
0 - 250
100
0 - 250
110
0 - 250
120
0 - 250
130
0 - 250
140
0 - 250
Manual, AA, A5E46373908A