Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 142

Advanced motor protection for type: 6sr variable frequency drives
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Advanced Motor Protection and RTD Protection Functions
6.28 Device 81 - Variable Pickup Overfrequency
Keypad Parameter Text
Tool Parameter Help Text
Minimum Speed
Variable Over Frequency w/ Min Speed Enable Point
Minimum Speed Reset
Variable Over Frequency w/ Min Speed Enable Speed
Reset Point
Startup Time
Variable Over Frequency w/ Min Speed Enable from
Startup
Picklist
Enable State
Variable Over Frequency Enable State
Advanced Motor Protection Menu - Variable Overfrequency Curve Menu (ID 7616)
Keypad Parameter Text
Tool Parameter Help Text
0% Speed Pickup
Define Pickup Level in % of Rated Hz at 0% Demanded
Speed
10% Speed Pickup
Define Pickup Level in %of Rated Hz at at 10% Deman‐
ded Speed
20% Speed Pickup
Define Pickup Level in % of Rated Hz at at 20% Deman‐
ded Speed
30% Speed Pickup
Define Pickup Level in % of Rated Hz at at 30% Deman‐
ded Speed
40% Speed Pickup
Define Pickup Level in % of Rated Hz at at 40% Deman‐
ded Speed
50% Speed Pickup
Define Pickup Level in % of Rated Hz at at 50% Deman‐
ded Speed
60% Speed Pickup
Define Pickup Level in % of Rated Hz at at 60% Deman‐
ded Speed
70% Speed Pickup
Define Pickup Level in % of Rated Hz at at 70% Deman‐
ded Speed
140
ID
Units
7641
%
7642
%
7643
ID
Units
Default
7644
Disabled
ID
Units
Default
7617
%
7618
%
7619
%
7620
%
7621
%
7622
%
7623
%
7624
%
Advanced Motor Protection for Variable Speed Operation
Default
Minimum - Maximum Val‐
Value
ue
0
0 - 100
10
0 - 100
5
0 - 6000
Values
Value
● Disabled
● Alarm
● LatchedAlarm
● Trip
Minimum - Maximum Value
Value
10
0 - 250
20
0 - 250
30
0 - 250
40
0 - 250
50
0 - 250
60
0 - 250
70
0 - 250
80
0 - 250
Manual, AA, A5E46373908A