Alarms, Faults, and Logging Messages

7.1
Alarms, Faults, and Logging Messages
The AMP function displays "AMP General Alarm" when an AMP function that is enabled as
either Alarm, Latched Alarm, or Block Start and has an active output. The function displays
"AMP General Fault" in the event that a function that is enabled as TRIP and has an active
output.
The "AMP General Alarm" and "AMP General Fault" do not describe the specific AMP function
that triggered the output. To view the specific function that triggered this alarm or fault, one must
either consult the Debug Screens "AMP Alarms/Faults" and "AMP Data", or the Event Log.
The Event Log displays which specific AMP function triggered the active General Alarm or
General Fault along with the exact time at which the event occurred. Siemens recommends
using the Event Log data as a diagnostic tool when investigating the cause of displayed
messages.
The following table contains the AMP functions and their associated Event Log Messages that
could trigger the AMP Alarm or Fault.
Note
All function outputs are visible at the networkms through manual IDs.
Table 7-1
Advanced Motor Protection Function Event Log Table
Function Name
Fixed UnderSpeed
Variable UnderSpeed
Fixed OverSpeed
Variable OverSpeed
Fixed UnderCurrent
Advanced Motor Protection for Variable Speed Operation
Manual, AA, A5E46373908A
Menu ID
Event Log Message
7217
Alarm: Fixed Under Speed
Fault: Under Speed
7226
Alarm: Variable Under Speed
Fault: Variable Under Speed
7181
Alarm: Fixed Over Speed
Fault: Fixed Over Speed
7189
Alarm: Variable Over Speed
Fault: Variable Over Speed
7256 (3 Phase)
Alarm: Fixed Under Current RMSA
Fault: Fixed Under Current RMSA
Alarm: Fixed Under Current RMSB
Fault: Fixed Under Current RMSB
Alarm: Fixed Under Current RMSC
Fault: Fixed Under Current RMSC