Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 75

Advanced motor protection for type: 6sr variable frequency drives
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

RTD 4 Menu (7452)
Keypad Parameter Text
Tool Parameter Help Text
RTD 4 Pickup Level
RTD 4 Pickup Level
RTD 4 Dropout Level
RTD 4 Percentage under Pickup Level for Reset
RTD 4 Pickup Delay
RTD 4 Pickup Delay
RTD 4 Dropout Delay
RTD 4 Time to Reset
Picklist
RTD 4 Usage
RTD 24 Bearing, Ambient, etc.
RTD 4 Output Type
RTD 4 Output Type Alarm, Fault, etc.
RTD 4 Failure Response
RTD 4 Response to a shorted or open RTD
RTD 5 Menu (7459)
Keypad Parameter Text
Tool Parameter Help Text
RTD 5 Pickup Level
RTD 5 Pickup Level
RTD 5 Dropout Level
RTD 5 Percentage under Pickup Level for Reset
RTD 5 Pickup Delay
RTD 5 Pickup Delay
RTD 5 Dropout Delay
RTD 5 Time to Reset
Advanced Motor Protection for Variable Speed Operation
Manual, AA, A5E46373908A
Advanced Motor Protection and RTD Protection Functions
6.16 Device 49RTD - Machine Thermal Overload - Fixed Pickup RTD Protection
ID
Units
Default
Value
7454
150 °C
● °C
● °F
7455
%
2
7456
sec
10
7457
sec
5
ID
Units
Default
Value
7453
None
7458
Disabled
7715
Alarm
ID
Units
Default
Value
7461
150 °C
● °C
● °F
7462
%
2
7463
sec
10
7464
sec
5
Minimum - Maximum Val‐
ue
0 - 572
0 -50
0 -180
0 - 180
Values
● Ambient
● Stator
● Bearing
● Other
● None
● Disabled
● Alarm
● LatchedAlarm
● Trip
● Block Start
● Alarm
● Trip
Minimum - Maximum Val‐
ue
0 - 572
0 -50
0 -180
0 - 180
73

Advertisement

Table of Contents
loading