NB!
Parameters 700-711 for the relay card are
only activated if a relay option card is in-
stalled in the VLT 6000 HVAC.
700
Relay 6, function
(RELAY6 FUNCTION)
703
Relay 7, function
(RELAY 7 FUNCTION)
706
Relay 8, function
(RELAY8 FUNCTION)
709
Relay 9, function
(RELAY9 FUNCTION)
Function:
This output activates a relay switch.
Relay outputs 6/7/8/9 can be used for showing status
and warnings. The relay is activated when the condi-
tions for the relevant data values have been fulfilled.
Activation/deactivation can be programmed in param-
eters 701/704/707/710 Relay 6/7/8/9, ON delay and
parameters 702/705/708/711 Relay 6/7/8/ 9, OFF de-
lay.
Description of choice:
See data choice and connections in Relay outputs .
701
Relay 6, ON delay
(RELAY6 ON DELAY)
704
Relay 7, ON delay
(RELAY7 ON DELAY)
707
Relay 8, ON delay
(RELAY8 ON DELAY)
710
Relay 9, ON delay
(RELAY9 ON DELAY)
Value:
0 - 600 sec.
Function:
This parameter allows a delay of the cut-in time of re-
lays 6/7/8/9 (terminals 1-2).
Description of choice:
Enter the required value.
= factory setting, () = display text, [] = value for use in communication via serial communication port
®
MG.61.B5.02 - VLT
is a registered Danfoss trademark
®
VLT
6000 HVAC Series
702
Relay 6, OFF delay
(RELAY6 OFF DELAY)
705
Relay 7, OFF delay
(RELAY7 OFF DELAY)
708
Relay 8, OFF delay
(RELAY8 OFF DELAY)
711
Relay 9, OFF delay
(RELAY9 OFF DELAY)
Value:
0 - 600 sec.
Function:
This parameter is used to delay the cut-out time of re-
lays 6/7/8/9 (terminals 1-2).
Description of choice:
Enter the required value.

Electrical installation of the relay card

The relays are connected as shown below.
Relay 6-9:
A-B make, A-C break
Max. 240 V AC, 2 Amp.
Max. cross-section: 1.5mm
Torque: 0.22 - 0.25 Nm.
Screw size: M2.
0 sec.
To achieve double isolation, the plastic foil must be
mounted as shown in the drawing below.
0 sec.
2
(AWG 28-16).
181