Danfoss VLT 6000 HVAC Series Design Manual page 134

Hide thumbs Also See for VLT 6000 HVAC Series:
Table of Contents

Advertisement

External Ref
- Ref
min
max
generates an output signal proportional to the resulting
reference value in the interval Minimum reference,
Ref
- Maximum reference, Ref
MIN
204/205).
FB
-FB
0-20 mA and
MIN
MAX
FB
-FB
4-20 mA and
MIN
MAX
FB
-FB
0-32000 p, an output signal propor-
MIN
MAX
tional to the reference value in the interval Minimum
feedback, FB
- Maximum feedback, FB
MIN
eters 413/414) is obtained.
0 - I
0-20 mA and
VLT, MAX
0 - I
4-20 mA and
VLT, MAX
0 - I
0-32000 p, an output signal proportional
VLT, MAX
to the output current in the interval 0 - I
tained.
0 - P
0-20 mA and
NOM
0 - P
4-20 mA and
NOM
0 - P
0-32000p, which generates an output signal
NOM
proportional to the present output power. 20 mA cor-
responds to the value set in parameter 102 Motor
power, P
.
M,N
0.0 - 100.0%
0 - 20 mA and
0.0 - 100.0%
4 - 20 mA and
0.0 - 100.0%
0 - 32.000 pulses which generates an
output signal proportional to the value (0.0-100.0%)
received by serial communication. Writing from Serial
communication is done to parameter 364 (terminal 42)
and 365 (terminal 45). This function is limited to the
following protocols: FC bus, Profibus, LonWorks FTP,
DeviceNet, Metasys N2 and Modbus RTU.
Fire Mode active is indicated on the output when ac-
tivated via input 16 or 17.
Fire Mode bypass is indicated on the output when
Fire Mode has been active and a certain trip occurred
(please see description of Fire Mode). A delay for this
indication can be programmed in parameter 432.
Please select Fire Mode bypass in parameter 430 to
enable this function.
320
Terminal 42, output, pulse scaling
(AO 42 PULS SCALE)
Value:
= factory setting, () = display text, [] = value for use in communication via serial communication port
134
0-32000 p which
(parameters
MAX
(param-
MAX
is ob-
VLT,MAX
®
VLT
6000 HVAC Series
1 - 32000 Hz
Function:
This parameter allows scaling of the pulse output sig-
nal.
Description of choice:
Set the desired value.
321
Terminal 45, output
(AO 45 FUNCTION)
Value:
See description of parameter 319 Terminal 42,
Output.
Function:
This output can function both as a digital or an analog
output. When used as a digital output (data value [0]-
[26]) it generates a 24 V (max. 40 mA) signal. For the
analog outputs (data value [27] - [41]) there is a choice
of 0-20 mA, 4-20 mA or a pulse sequence.
Description of choice:
See description of parameter 319 Terminal 42, Output.
322
Terminal 45, output, pulse scaling
(AO 45 PULS SCALE)
Value:
1 - 32000 Hz
Function:
This parameter allows scaling of the pulse output sig-
nal.
Description of choice:
Set the desired value.
®
MG.61.B5.02 - VLT
is a registered Danfoss trademark
5000 Hz
5000 Hz