TECHNICAL DATASHEET
PMT Panel Mount Power Supply
48V 350W 1 Phase / PMT-48V350W1A
Assembly & Installation
Side Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 5mm
4). This is to maintain a safety distance between the screw and internal components.
Base Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 4mm (0.16 inch) length (Refer to Fig.
4).
Connector
This surface belongs to customer's end system or panel where the power supply is mounted.
Base Mounting (Horizontal)
Use flexible cable (stranded or solid) of AWG No. 22-12. The input/output connectors' allowable current is 23A max per pin. User
should calculate and select the suitable wire specification (type/quantity/diameter) according to actual output current. The torque at
the connector shall not exceed 13Kgf.cm
Recommended mounting torque of the product and its mounting accessories is 9~12Kgf.cm (7.81~10.42 lbf.in).
Fig. 3
Mounting Hole Locations and the Safety Distance
For safety reasons, please ensure the mounted device is kept at ≥ 4mm (0.16 inch) safety distance at all sides from other components
and equipments. In addition, to ensure sufficient convection cooling, always maintain a distance of ≥ 20mm (0.79 inch) from fan ventilated
surfaces while the device is in operation. Please insert an insulation sheet between the system and product, if the safety distance is <
4mm (0.16 inch).
Fig. 4
Assembly Reference
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
9
www.DeltaPSU.com (November 2018, Rev. 04)
Base Mounting (Vertical)
Fig. 2
Mounting Orientation
(11.23
lbf.in). The insulation stripping length should not exceed 0.275" or 7mm.
Only use M4 screw ≤ 5 mm (0.20 inch) through the base mounting holes
at Ⓐ. This is to keep a safe distance between the screw and internal
components.
Only use M4 screw
at Ⓑ.
□□
(0.20 inch)
Side Mounting (Horizontal)
Safety Distance
D1 = 4mm Min.
D2 = 20mm Min.
≤ 4 mm (0.16 inch) through the base mounting holes