Mdar Settings (Non-Pilot System); Trip Time Constants For Co Curves - ABB REL-300 Instruction Leaflet

Numerical distance protection (mdar) relaying system
Hide thumbs Also See for REL-300:
Table of Contents

Advertisement

TABLE 6-1. MDAR SETTINGS (NON-PILOT SYSTEM)
VERS
OSC
FDAT
CTR
VTR
FREQ
CTYP
RP
XPUD
DTYP
TTYP
62T
Z1RI
Z2RI
Z3RI
STYP
Z1P
Z1G
T1
Z2P
T2P
Z2G
T2G
Z3P
T3P
GBPU
T3G
NOTE: This MDAR settings table is for 60 Hz and 5A ct systems. For 1A ct, change Z1P, Z1G, Z2P, Z2G,
Z3P, Z3G, RT, RU by multiplying a factor of 5, and all current values mentioned in the text
should be multiplied by a factor of 0.02.
TABLE 6-2. TRIP TIME CONSTANTS FOR CO CURVES
Curve #
T
o
CO2
111.99
CO5
8196.67
CO6
784.52
CO7
524.84
CO8
477.84
CO9
310.01
CO11
110.
(5/92)
0
TRIP
TRIP
1000
2000
60
5
NO
.5
KM
OFF
5.000 *
YES
NO
NO
3ZNP
4.5
4.5
NO
OUT
1.00
OUT
1.50
OUT
* For Single-Pole trip option only.
2.00
** For Out-of-Step Block option only.
0.5
2.50
K
735.00
13768.94
671.01
3120.56
4122.08
2756.06
17640.00
Z3FR
PANG
GANG
ZR
LV
IL
IOS
IOM
ITP
ITG
OSB
OSOT
RT
RU
DIRU
GBCV
GTC
GDIR
CIF
LOI
AL2S
LLT
LOPB
SETR
TIME
C
P
0.675
1
1.13
1
1.19
1
0.8
1
1.27
1
1.35
1
0.5
2
I.L. 40-385.1B
FWD
75
75
3.0
60
.5
.5
.5
OUT
OUT
NO **
4000 **
15.00
15.00 **
ZSEQ
OUT
24
YES
NO
NO
NO
NO
NO
NO
NO
R
501
22705
1475
2491
9200
9342
8875
6-19