Setting Display - ABB REL-300 Instruction Leaflet

Numerical distance protection (mdar) relaying system
Hide thumbs Also See for REL-300:
Table of Contents

Advertisement

I.L. 40-385.1B
Information/Settings
Software version
Oscillographic data initiation
Fault data initiation
ct ratio
PT ratio
Rated freq.
ct secondary rating
Enable/disable readouts
in primary I & V values
Reactance for fault location
(ohms per unit distance)
Fault location, displayed in km or miles
Reclosing mode
1. 3PT on all faults, no RI
2. 3PT on all faults, with 3RI on φGF
3. 3PT on all faults, with 3RI on φGF/2φF
4. 3PT on all faults, w/3RI
5. SPT on φGF with SRI
3PT on MφF without RI
6. SPT on φGF with SRI
3PT on MφF with 3RI
Single phasing limit timer
RI on Z1T
RI on Z2T
RI ON Z3T
Breaker Failure Reclose block
Pilot logic control
Pilot system selection:
1. Non-Pilot, 3-zone distance
2. Zone-1 extension
3. Permissive overreach transfer trip
or unblocking
4. Permissive underreach transfer trip
5. Blocking
Forward Direction Ground Timer
Weakfeed Enable
3-Terminal Line Application
Blocking system channel
coordination timer
Reverse block sw.
Pilot phase setting
Pilot ground setting
*Optional
4-10
TABLE 4-1. SETTING DISPLAY
Function Field
VERS
OSC *
FDAT
CTR
VTR
FREQ
CTYP
RP
XPUD
DTYP
TTYP
62T *
Z1RI
Z2RI
Z3RI
BFRB *
PLT *
STYP
FDGT *
WFEN *
3TRM *
BLKT *
RBSW *
PLTP *
PLTG *
(SHEET 1 OF 3)
Displayed at
Value Field
(using 5 A ct and 60 Hz)
(SEE NOTE ON SHEET 3)
numerical (0,1)
TRIP/Z2TR/Z2Z3/∆V∆I
TRIP/Z2TR/Z2Z3
30-5000 (5)
300-7000 (10)
60, 50
5 or 1
YES/NO
0.300-1.500, in 0.001/DTYP
KM or MI (miles)
OFF
1PR
2PR
3PR
SPR
SR3R
0.300-5000, in 0.050 sec. steps
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
3ZNP
Z1E
POTT
PUTT
BLK
BLK, 0 to 15 cycles in 1cycle steps
YES/NO
YES/NO
0-98, in 2 ms steps
Omitted
OUT, 0.01-50.00 in 0.01 Ω steps
OUT, 0.01-50.00 in 0.01 Ω steps
(5/92)