I.L. 40-385.1B
Information/Settings
CIF trip/stub bus protection
LLT trip
LOP block
LOI Block
Alarm 2 (Trip) Seal-In
Remote Setting
Real Time Clock
1. Set Year
2. Set Month
3. Set Day
4. Set Weekday
5. Set Hour
6. Set Minute
NOTE: WHEN THE CTYP FUNCTION IS SET AT 1 AMPERE, THE RANGE OF THE FOLLOWING FUNC-
TIONS ARE AS SHOWN BELOW:
• ZIP/ZIG/Z2P/Z2G Z3P/Z3G/PLTP/PLTG
• ITP/ITG
• IL/IOS/IOM
NOTE: SEE ALSO SECTION 5.2.4, SELECTIONS OF CTYP SETTINGS.
NOTE: SEE PREFACE FOR INFORMATION ON SETTING NOMENCLATURE APPLIQUES.
NOTE: The increments of timers are based on the line frequency, e.g., 16 msec for 60 Hz and 20 msec
for 50 Hz (to the nearest msec)
4-12
TABLE 4-1. SETTING DISPLAY
Function Field
CIF
LLT
LOPB
LOIB
AL2S
SETR
TIME
YEAR
MNTH
DAY
WDAY
HOUR
MIN
(SHEET 3 OF 3)
Displayed at
Value Field
(using 5 A ct and 60 Hz)
(SEE NOTE)
CIFT/STUB/BOTH/NO
YES/FDOG/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
1980-2079, in 1 year steps
1-12, in 1 month steps
1-31 in 1 day steps
Sun, Mon, Tues,
Wed, Thur, Fri, Sat
0-24, in 1 hour steps
0-60, in 1 minute steps
0.05-250.00, in 0.05 Ω steps
0.4-30.0, in 0.1 A steps
0.1-2.0, in 0.02 A steps