2.1
TECHNICAL
Operating Speed
(from fault detection
to trip contact close
-60 Hz)
ac Voltage (VLN) at 60 Hz
ac Current (In)
Rated Frequency
Maximum Permissible ac Voltage
• Continuous
• 10 Second
Maximum Permissible ac Current
• Continuous
• 1 Second
Typical Operating Current
dc Battery Voltages
Nominal
48/60 Vdc
110/125 Vdc
220/250 Vdc
dc Burdens: Battery
ac Burdens:
Volts per Phase
Current per Phase
(5/92)
Section 2. SPECIFICATIONS
(VLN) at 50 Hz
I.L. 40-385.1B
12-14 ms (minimum)
22 ms (typical)
70
Vrms
63.5 Vrms
1 or 5 A
50 or 60 Hz
1.5 x nominal voltage
2.5 x nominal voltage
3 x Nominal Current
100 x Nominal Current
0.5 A
Operating Range
38 - 70 Vdc
88- 145 Vdc
176 - 290 Vdc
7 W normal
30 W tripping
0.02VA at 70 Vac
0.15VA at 5 A