B Technical Data; General Data (Mechanical And Ambient Conditions); Power Supply; Connection Cables And Cable Glands - Honeywell FE260 Operating Instructions Manual

Function expansion unit
Table of Contents

Advertisement

28
B
Technical data
B-1

General data (mechanical and ambient conditions)

Housing/structure ...........................
Dimensions (W x H x T) .................
Cable union glands ........................
Weight ............................................
Protection .......................................
Ambient temperature .....................
Climatic conditions .........................
B-2

Power supply

Designation ....................................
Cable connection ...........................
Cable cross-sectional area ............
Screening .......................................
Voltage ...........................................
Power consumption .......................
B-3

Connection cables and cable glands

In order to ensure the IP protection class 65 according to EN60529 even when all connection cables are
mounted, the values in the following table must be taken into account:
Cable gland
Plastic cable gland M16
a"
(page 9, fig. 4. pos. „
Plastic cable gland M12
b"
(page 9, fig. 4. pos. „
Metal cable gland M20
c"
(page 9, fig. 4. pos. „
Take care that only one core is inserted into each clamp!
The cable cores must be stripped 11 mm. They must be inserted into the terminal over a length of 14 mm!
Operating Manual
Wall-mounted housing,
Aluminium cast alloy G AI SI 12 / DIN 1775
approx. 290 x 175 x 102 mm
with cable entry glands and hinges
Suitable for cables with overall diameter 6...10 mm
approx. 3 kg
IP 65 according to EN60529
„AC" versions:
„DC" version:
Relative humidity max. 93%, non-condensing
„230V"
„115V"
„10...30V"
Screw terminals, green, for
solid wires
flexible stranded wire 0.14...1.5 mm²
Fit wire-end sleeves to flexible stranded wires
No cable screen required
230 V AC +10% / -15%
115 V AC +10% / -15%
10 V DC to 30 V DC
3 W
Valid cable diameter
range
7 ... 8 mm
)
5 ... 6 mm
)
7 ... 8 mm
)
0°C ... +40 °C
-10°C ... +60 °C
(„AC" version 230 V)
(„AC" version 115 V)
(„DC" version)
0.14...2.5 mm²
(„AC" version 230 V)
(„AC" version 115 V)
(„DC" version)
max. (with modem)
Torque for tightening the
gland
2,5 Nm
1,5 Nm
10 Nm
FE260
Metric wrench size of
open-end wrench
22 mm
15 mm
20 mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents