MCD 200 DeviceNet Option

This requires an MCD DeviceNet Module which clips onto the side
of the MCD 200 (Cat. No: 175G9002).
MCD200
Cat. No: 175G9002
Notes
• A single DeviceNet Module is required for each MCD 200.
• DeviceNet node address (MAC ID) and data rate are selected
using three rotary switches on the DeviceNet Module.
• Up to 63 DeviceNet Modules can be used as DeviceNet slaves
on a single DeviceNet network.
• The DeviceNet Module is powered via the network cable.
• The MCD DeviceNet Module is ODVA tested and certified.
• For more information on the MCD DeviceNet Module, refer to the
Installation Instructions (MG.17.Hx.02), located at
www.danfoss.com/drives.
MCD
DeviceNet
Module
(V+)
RD
(CAN-H)
WH
(SHIELD)
(CAN-L)
BU
(V-)
BK
Standard 5-wire
connection onto a
DeviceNet network.
120 termination
resistors are required
at end of each end
of the network cable.