Power Supply - Endress+Hauser Cerabar T PMP 13 Technical Information

Pressure transducer for hygienic processes
Table of Contents

Advertisement

Cerabar T PMP 135
Output signal
Output current
Power
Switch frequency
Input PLC
Inductive loads
Cable entry
Endress+Hauser
Switch output
Positive voltage signal (rate depends on power supply voltage) at electronics switch output
(PNP).
≤ 500 mA
Switch status ON: I
a
≤ 1 mA
Switch status OFF: I
a
max. 6 W
max. 10 Hz
≤ 2 kΩ
Input resistance R
i
≥ 10 mA
Input current I
i
To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid val-
ves) when directly connected to a protective circuit (free-wheeling diode or capacitor).

Power supply

Plug with Pg 11 or ½ NPT gland
➀ Plug-in housing
➁ Plug-in jack with gasket
➂ Coupling nut
➃ Plug with O-ring
➄ Operating potentiometer (inner)
M 12x1 plug
➀ Coupling nut
➁ Connector with gasket
➂ Operating potentiometer (inner)
P01-PMx13xxx-04-xx-xx-xx-001
5 m cable, only analogue output
➀ Reference pressure line