Degree of protection
Vibration resistance
Electromagnetic
compatibility
Medium temperature
Limiting medium pressure
range
Design, dimensions
6
•
with plug with Pg 11 or ½ NPT gland: IP 65
•
with M 12x1 plug when using gauge pressure sensors: IP 65
with M 12x1 plug when using absolute pressure sensors: IP 68 (1 m water column)
•
with cable: IP 68 (1 m water column)
4M5 as per DIN EN 60721-3
Interference emission as per EN 61326 electrical device B,
Interference immunity as per EN 61326 appendix A (industrial use) and NAMUR recommendation
NE 21.
Operating conditions: Process
–25...+100 °C (+135 °C for max. 1 hour)
– For overload resistance see "Ordering information" section
– Vacuum resistance up to 10 mbar
Mechanical construction
A = height dimension of process connections (see following section)
(all dimensions in mm / 25.4 mm = 1 in)
•
Plug version with Pg 11 or ½ NPT gland as per DIN 43650A/ISO 4400
•
M 12x1 plug version
•
Cable version, cable length of 5 m with cable outer diameter of 5.8 mm; wires 4 x 0.22 mm
reference pressure hose with outer diameter of 2 mm
abs
Cerabar T PMP 135
P01-PMP13xxx-06-xx-xx-xx-002
2
;
Endress+Hauser