Motorized Linear Actuator

7.4 Configuration of the DIP switches

The factory setting of the DIP switches is position 0, as shown.
Switch
Function
DIP 1
Set value input: voltage, V or current, mA?
DIP 2
Set value input starting at 0 V / 0 mA or
2 V / 4 mA?
DIP 3
Analogue output starting at 0 V / 0mA or
2 V / 4 mA?
DIP 4
Direction of control action: valve closed with
drive spindle extended or retracted?
DIP 5
Current position of the actuator is saved as
additional switching position "2EZ-1". See
wiring diagram, page 22.
DIP 6
Current position of the actuator is saved as
second additional switching position "2EZ-1".
See wiring diagram, page 22.
DIP 7, 8, 9
These 3 DIP switches define the function:
linear / split range / 11-point / inverted
DIP 10
Defines valve characteristic using actuator
characteristic, see page 26.
DIP 11
Selects standard or Modbus mode.
DIP 12
Starts initialization run.
Set back to 0 after initialization
(s. section 7.5.2)
N↔S
Selects normal or safety mode
Fig. 26: Setting the DIP switches
W. Baelz & Sohn GmbH & Co. · Koepffstrasse 5 · 74076 Heilbronn · Germany · www.baelz.de
baelz 373-E07
Position 1 "ON"
current, mA
2-10 V / 4-20 mA
2-10 V and / or
4-20 mA
Drive spindle retracted
valve closed
Actuator characteristic
inverse equal
percentage, valve
action linear
Modbus mode
position "S"
= safety mode
= factory setting
Position 0
voltage, V
0-10 V / 0-20 mA
0-10 V and / or
0-20 mA
Drive spindle
extended →
valve closed
from 0 to 1 →
save "2EZ-1"
= 2%
from 0 to 1 →
save "2EZ-2"
= 98%
s. Fig. 27, page 26
= linear
Actuator characteristic
linear, valve action
equal percentage
standard mode
from 0 to 1 →
starts initialization run
position "N"
= normal mode