Examples - GE AF-650 GP Design Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

10.5 Examples

All parameters in the AF-650 GP are named with one or two letters, a "-" and
a number e.g. F-07. To access parameters the following table has to be used
because letters cannot be addressed.
Example: F-07 = 7, E-01 = 101, DR-53 = 1253.
10
10.5.1 Writing a Parameter Value
Change par. F-15 Motor Speed High Limit [Hz] to 100 Hz.
Write the data in EEPROM.
PKE = E00F Hex - Write single word in par. F-15 Motor Speed High Limit [Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see Con-
version.
188
Letter
F
E
C
P
H
K
AN
B
O
PB
SP
XC
DR
LG
CL
ID
AP
T
FB
PC
AO
BP
DN
PI
LC
EC
RS
BN
LN
EN
CB
CA
CD
The telegram will look like this: