Bit 13/14, Selection of set-up:
Use bits 13 and 14 to choose from the four menu set-ups according to the
shown table: .
The function is only possible when Multi Set-Ups is selected in par. K-10 Active
Set-up.
Make a selection in par. O-55 Set-up Select to define how Bit 13/14 gates with
the corresponding function on the digital inputs.
Bit 15 Reverse:
Bit 15 = '0': No reversing. Bit 15 = '1': Reversing. In the default setting, reversing is set to digital in par. O-54 Reversing Select. Bit 15 causes reversing only when Ser.
communication, Logic or or Logic and is selected.
10.10.2 Status Word According to Drive Profile (STW) (par. O-10 Control Word Profile = Drive profile)
Bit
Bit = 0
00
Control not ready
10
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
Speed ≠ reference
08
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Explanation of the Status Bits
Bit 00, Control not ready/ready:
Bit 00 = '0': The frequency converter trips. Bit 00 = '1': The frequency converter controls are ready but the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready:
Bit 01 = '1': The frequency converter is ready for operation but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = '0': The frequency converter releases the motor. Bit 02 = '1': The frequency converter starts the motor with a start command.
Bit 03, No error/trip:
Bit 03 = '0' : The frequency converter is not in fault mode. Bit 03 = '1': The frequency converter trips. To re-establish operation, enter [Reset].
198
Set-up
Bit 14
1
0
2
0
3
1
4
1
Bit = 1
Control ready
Drive ready
Enable
Trip
Error (no trip)
-
Triplock
Warning
Speed = reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
AF-650 GP Design Guide
Bit 13
0
1
0
1