GE AF-650 GP Design Manual page 194

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Coil Number
Description
1-16
Frequency converter control word (see table below)
17-32
Frequency converter speed or set-point reference Range 0x0 – 0xFFFF (-200% ... ~200%)
33-48
Frequency converter status word (see table below)
49-64
Open loop mode: Frequency converter output frequency Closed loop mode: Frequency con-
verter feedback signal
65
Parameter write control (master to slave)
0 =
1 =
66-65536
Reserved
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Frequency converter control word (Drive profile)
Holding registers
Register Number
Description
00001-00006
Reserved
00007
Last error code from an Drive data object interface
00008
Reserved
00009
Parameter index*
00010-00990
000 parameter group (parameters 001 through 099)
01000-01990
100 parameter group (parameters 100 through 199)
02000-02990
200 parameter group (parameters 200 through 299)
03000-03990
300 parameter group (parameters 300 through 399)
04000-04990
400 parameter group (parameters 400 through 499)
...
...
49000-49990
4900 parameter group (parameters 4900 through 4999)
50000
Input data: Frequency converter control word register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: Frequency converter status word register (STW).
50210
Output data: Frequency converter main actual value register (MAV).
* Used to specify the index number to be used when accessing an indexed parameter.
Parameter changes are written to the RAM of the frequency converter
Parameter changes are written to the RAM and EEPROM of the frequency
converter.
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
Signal Direction
Master to slave
Master to slave
Slave to master
Slave to master
Master to slave
Coil
0
33
Control not ready
34
Frequency converter not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Frequency converter status word (Drive profile)
AF-650 GP Design Guide
1
Control ready
Frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
193
10