Download Print this page

Danfoss CD302 Instructions Manual page 3

Frequency converter, inverter reciprocating compressors vtz

Advertisement

Instructions
•Accessory Bag ≤ 7.5 kW, IP55
Mechanical Dimension
Height of black plate
A
Distance between
a
mounting holes
Width of black plate
B
Distance between
b
mounting holes
Depth without option A/B
C
Depth with option A/B
C
c
d
e
f
© Danfoss | DCS (CC) | 2019.04
• Accessory Bag 11 – 22 kW
Mechanical mounting
1) Drill holes in accordance with the measure-
ments given.
2) You must provide screws suitable for the sur-
face on which you want to mount the CD 302.
Retighten all four screws.
Mechanical dimensions
Frame size A2
Frame size A3
3.0 kW (200-240 V)
4.0 kW (380-480 V)
5.5 - 7.5 kW (380-480 V)
4 kW (525-600 V)
5.5 - 7.5 kW (525-600 V)
IP 20
IP 20
268 mm
268 mm
257 mm
257 mm
90 mm
130 mm
70 mm
110 mm
205 mm
205 mm
220 mm
220 mm
8.0 mm
8.0 mm
ø 11 mm
ø 11 mm
ø 5.5 mm
ø 5.5 mm
9 mm
9 mm
Frame size A5
4.0 kW (200-240 V)
4.0 - 7.5 kW (380-480 V)
IP 55
Height
420 mm
402 mm
Width
242 mm
215 mm
Depth
195 mm
195 mm
Screw holes
8.25 mm
ø 12 mm
ø 6.5 mm
9 mm
CD 302 IP20 allows side-by-side installation.
Because of the need for cooling, there must be a
minimum of 100 mm free air passage above and
below the CD 302.
The back wall must always be solid. All CD302 are
equiped of a back metal plate to garantee proper
heat exchanger ventilation. Never remove this
metal sheet.
Safety Requirements of Mechanical Installa-
tion
The frequency converter is cooled by means of air
circulation.
To protect the unit from overheating, it must be
ensured that the ambient temperature does not
exceed the maximum temperature stated for the
frequency converter and that the 24-hour ave-
rage temperature is not exceeded. If the ambient
temperature is in the range of 45°C - 55°C, dera-
ting of the frequency converter will become rele-
vant. The service life of the frequency converter
is reduced if derating for ambient temperature is
not taken into account.
Frame size B1
Frame size B2
5.5 - 7.5 kW (200-240 V)
11kW (200-240 V)
11-15 kW (380-480 V)
18.5-22 kW (380-480 V)
IP 21 / IP 55
IP 21 / IP 55
480 mm
454 mm
242 mm
210 mm
260 mm
260 mm
12 mm
ø 19 mm
ø 9 mm
9 mm
AN000086420674en-000201 | 3
650 mm
624 mm
242 mm
210 mm
260 mm
260 mm
12 mm
ø 19 mm
ø 9 mm
9 mm