Instructions
Other ways of doing the installation may have just
as good an EMC performance, provided the above
guide lines to engineering practice are followed.
• EMC Correct Installation of an IP20 CD302
• Safety earth connection
The frequency converter has a high leakage cur-
rent and must be earthed appropriately for safety
reasons acording to EN 50178.
© Danfoss | DCS (CC) | 2019.04
If the installation is not carried out according
to the guideline and if unscreened cables and
control wires are used, some emission require-
The earth leakage current from the frequency
converter exceeds 3.5 mA. To ensure a good me-
chanical connection from the earth cable to the
earth connection (terminal 95), the cable cross-
ments are not complied with, although the im-
munity requirements are fulfilled. See the para-
graph EMC test results.
section must be at least 10 mm2 or 2 rated earth
wires terminated separately.