Maintenance and servicing
9.5 Restore factory setting
9.5.1

Restoring the factory settings via High Feature 3RW5 HMI

Requirements
● Access protection to 3RW5 HMI High Feature is not active or has been removed.
● You are in menu "Parameters > Factory Settings"
● The 3RW5 HMI High Feature (LOCAL) has control priority.
Procedure
1. Select the desired menu item.
– 3RW5 soft starter
– Communication module
– 3RW5 HMI High Feature
– All
2. Confirm the menu item.
Result
The factory setting of the selected device or all devices is restored.
Note the effects of the factory settings described in Chapter Restore factory setting
(Page 151).
152
SIRIUS 3RW52 Soft Starter
Manual, 01/2019, A5E35630451002A/RS-AD/004