Troubleshooting
5.2 Status LED overview
Number
Cause
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
A30502
DC link overvoltage
A30920
Temperature sensor fault
For further information, please refer to the List Manual.
5.2
Status LED overview
LED status indicators
The Control Unit has number of dual-colour LEDs which are designed to indicate the
operational state of the Inverter. The LEDs are used to indicate the status of the following
states:
● General fault conditions
● Communication status
● Input and Output status
● Safety-Integrated status
The location of the various LEDs on the Control Unit are shown in the figure below.
60
Remedy
Check the converter's input fuses.
Check the motor cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might be
broken).
Check the supply voltage on the input terminals.
Check the line voltage setting (p0210).
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases
Check the internal fan and if required replace.
Check the internal fan and if required replace.
Check the device supply voltage (p0210).
Check the line reactor dimensioning
Check that the sensor is connected correctly.
Getting Started, FW V4.5, A5E03404762A AB