No.
Parameter Description
7
Crystalline
This parameter
silicon PV
reduces the DC
compensati
voltage of PV modules
on mode
to the PE by reducing
the impedance of the
SUN2000 input side to
the PE, thereby
effectively reducing
PID effect of PV
modules.
8
Communic
The standards of
ation
certain countries and
interrupt
regions require that
shutdown
the SUN2000 must
shut down after the
communication is
interrupted for a
certain time.
9
Communic
Specifies the duration
ation
for determining
Issue 04 (2018-06-01)
Default
Unit
Value
N/A
Output
disabled
N/A
Disable
min
30
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Man-Machine Interactions
Value Range
Remarks
Output
This parameter is
disabled
displayed if PV
module type is set
P-type output
to Crystalline
N-type output
silicon. Set this
parameter to P-type
output for P-type
PV modules and
N-type output for
N-type PV modules.
Disable
If Communication
interrupt
Enable
shutdown is set to
Enable and the
SUN2000
communication has
been interrupted for
a specified time (set
by Communication
interruption
duration), the
SUN2000 will
automatically shut
down.
[1, 120]
N/A
quickly
restart in 60
minutes when
the input
power of PV
modules
drops
drastically
due to
shading.
If PV module
type is set to
CPV 2, the
inverter can
quickly
restart in 10
minutes when
the input
power of PV
modules
drops
drastically
due to
shading.