Huawei SUN2000-45KTL-US-HV-D0 User Manual page 108

Hide thumbs Also See for SUN2000-45KTL-US-HV-D0:
Table of Contents

Advertisement

SUN2000-45KTL-US-HV-D0
User Manual
Parameter description
No.
Paramete
Description
r
1
LVRT
When the power grid
voltage is abnormally
low for a short time,
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called LVRT.
2
LVRT
Specifies the threshold
threshold
for triggering LVRT.
LVRT
Specifies whether to
3
undervolta
shield the
ge
undervoltage
protection
protection function
shield
during LVRT.
4
LVRT
During LVRT, the
reactive
SUN2000 needs to
power
generate reactive
compensati
power to support the
on power
power grid. This
factor
parameter is used to
set the reactive power
generated by the
SUN2000.
High
When the power grid
5
voltage
voltage is abnormally
ride-throug
high for a short time,
h
the SUN2000 cannot
disconnect from the
power grid
immediately and has
to work for some time.
This is called high
voltage ride-through
(HVRT).
6
Active
Specifies whether to
islanding
enable the active
islanding protection
function.
Voltage
The standards of
7
rise
certain countries and
Issue 04 (2018-06-01)
Unit
Default
Value
N/A
The default
value varies
with the grid
code. The
displayed
value prevails.
V
80%Vn
The default
N/A
value varies
with the grid
code. The
displayed
value prevails.
N/A
2
N/A
Disable
N/A
Enable
N/A
Disable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Man-Machine Interactions
Value Range
Remarks
Disable
N/A
Enable
[50%Vn,
Vn represents the
92%Vn]
rated voltage.
Disable
N/A
Enable
[0, 3]
For example, if you
set LVRT reactive
power
compensation
power factor to 2,
the reactive current
generated by the
SUN2000 is 20%
of the rated current
when the AC
voltage drops by
10% during LVRT.
Disable
N/A
Enable
Disable
N/A
Enable
Disable
N/A
102