Table 6-2 Cable specifications
Cable Specifications
Conductor
cross-sectional area
Cable outer diameter range
supported by the AC OUTPUT
waterproof connector
Procedure
Step 1 Remove an appropriate length of the jacket and insulation layer from the AC output power
cable using a wire stripper.
Ensure that the jacket is in the maintenance compartment.
Figure 6-8 Three-core cable (excluding the ground cable)
(A) Core wire
Issue 04 (2018-06-01)
If you connect a ground cable to the PE point on the chassis, you are advised to use a
three-core (L1, L2, and L3) outdoor cable.
If you connect a ground cable to the PGND point in the maintenance compartment, you
are advised to use a four-core (L1, L2, and L3) outdoor cable.
Table 6-2
describes the cable specifications.
Range
Recomm
ended to
use
OT terminal: M8 (L1, L2, and L3) and M6 (PE).
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Copper-Core Cable
6–2/0 AWG
4 AWG
37–44 mm (1.46–1.73 in.)
(B) Insulation layer
6 Electrical Connections
Copper-Clad
Aluminum Cable or
Aluminum Alloy
Cable
4–2/0 AWG
2 AWG
(C) Jacket