Figure 6-17 Measuring voltage
If the voltage is a negative value, the DC input polarity is incorrect. Correct the polarity.
If the voltage is greater than 1500 V, too many PV modules configured to the same string.
Remove some PV modules.
Step 4 Pull out the blue dustproof plugs from the ends of the DC input connectors.
Before performing
Step 5 Insert the positive and negative connectors into the corresponding positive and negative DC
input terminals of the SUN2000 until they snap into place.
Issue 04 (2018-06-01)
Step
5, ensure that the two DC switches are OFF.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Electrical Connections
55