SUN2000-45KTL-US-HV-D0
User Manual
No.
Parameter
protection time
23
Level-4 OV
protection
Level-4 OV
24
protection time
25
Level-3 UV
protection
26
Level-3 UV
protection time
Level-4 UV
27
protection
28
Level-4 UV
protection time
8.2.2.3 Setting Feature Parameters
Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings screen.
Figure 8-7 Feature Parameters (special user)
----End
Issue 04 (2018-06-01)
Description
protection duration.
Specifies the level-4 overvoltage
protection threshold.
Specifies the level-4 overvoltage
protection duration.
Specifies the level-3 undervoltage
protection threshold.
Specifies the level-3 undervoltage
protection duration.
Specifies the level-4 undervoltage
protection threshold.
Specifies the level-4 undervoltage
protection duration.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Man-Machine Interactions
Unit
Value Range
V
[1 x Vn, 1.36 x Vn]
ms
[50, 720000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 720000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 720000]
101