User Manual
Figure 8-5 Grid Parameters (special user)
----End
Parameter List
No.
Parameter
1
Grid code
Auto start upon
2
grid recovery
3
Grid
connection
duration after
power grid
recovery
4
Grid
reconnection
voltage upper
limit
Issue 04 (2018-06-01)
Description
Set this parameter based on
the grid code of the country
or region where the
SUN2000 is used and the
SUN2000 application
scenario.
Specifies whether to allow
the SUN2000 to
automatically start after the
power grid recovers.
Specifies the waiting time
for SUN2000 restart after
the power grid recovers.
The standards of certain
countries and regions require
that the SUN2000 must not
export power to the power
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Unit
Default Value
N/A
IEEE
1547a-MV600
N/A
Enable
s
The default value
is 60 if the
1547a-MV600
grid code is
selected. The
default value is
300 if another
grid code is
selected.
V
The default value
varies with the
grid code. The
displayed value
8 Man-Machine Interactions
Value Range
N/A
Disable
Enable
[0, 900]
[100%Vn, 136%Vn]