Huawei SUN2000-45KTL-US-HV-D0 User Manual page 63

Hide thumbs Also See for SUN2000-45KTL-US-HV-D0:
Table of Contents

Advertisement

SUN2000-45KTL-US-HV-D0
User Manual
embedded WebUI, or the network management software (such as the NetEco) on the PC to
query information about the SUN2000, such as energy yield, alarms, and running status.
PLC Communication
The PLC communication board loads communication signals onto power cables for
transmission. For details about how to install the PLC, see the PLC CCO01A User Manual or
SmartLogger2000 User Manual.
Issue 04 (2018-06-01)
Figure 6-19
shows the communication mode for a single SUN2000.
Figure 6-19 Communication mode for a single SUN2000
Figure 6-20
shows the communication mode for multiple SUN2000s.
If multiple SUN2000s are used, connect all the SUN2000s in daisy chain mode over an
RS485 communications cable.
Figure 6-20 Communication mode for multiple SUN2000s
The RS485 communication distance between the SUN2000 at the end of the daisy chain and the
SmartLogger cannot exceed 1000 meters.
If multiple SUN2000s need to communicate with one another and are connected to a PC over the
SmartLogger2000, a maximum of six daisy chains can be configured.
To ensure the system response speed, it is recommended that the number of devices on each daisy
chain be less than 30.
The built-in PLC module in the SUN2000 does not need to be connected with cables.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.